# HVAC Mapping Gaps Found In BOSS

Gaps between BuildingSync audit data and the `buildingsync-measures-gem` [HVAC Mapping and Migration Guide](https://github.com/BuildingSync/buildingsync-measures-gem/blob/develop/docs/HVAC_MAPPING_AND_MIGRATION.md), found while running `BOSS::HvacTopologySelector` on BOSS fixtures. To be moved to `buildingsync-measures-gem`. Rows the guide already lists as mapping gaps or not mappable (fan-powered VAV with electric reheat, water-loop and ground-source heat pumps, chilled beam, radiant, ERV/HRV, exhaust, natural ventilation) are not repeated here.

Fixture paths are under `spec/files/v2.7.0/`.

Status: gaps 1-7 were resolved upstream in buildingsync-measures-gem `e1b2f33` and gap 8 in `5e775a6`; all are adopted in `BOSS::HvacTopologySelector`.

## Measure Gaps

### 1. Packaged unitary heat pump with gas backup

- Data: `example-smalloffice-level2.xml`, all five deliveries. `HeatPumpType = Packaged Unitary`, `HeatPumpBackupSystemFuel = Natural gas`, single-zone CAV delivery.
- Guide: the Packaged Rooftop Heat Pump row requires `HeatPumpBackupSystemFuel = Electricity`. No row covers gas backup, so the delivery identifies no configuration.
- Measure: `hvac_packaged_rooftop_heat_pump` creates electric supplemental heat only.
- Ask: add a gas-supplemental option to the measure and a guide row, or list gas-backup packaged heat pumps as not mappable.

### 2. Packaged rooftop AC with `FurnaceType = Other`

- Data: `Reference-PrimarySchool-L200-Audit.xml`, PSZAC deliveries. Gas furnace (`PrimaryFuel = Natural gas`, `HeatingMedium = Air`) with `FurnaceType = Other`, packaged RTU DX, single-zone CAV.
- Guide: the Packaged Rooftop Air Conditioner and Warm Air Furnace rows require `FurnaceType = Warm air`.
- Ask: decide whether `Other` (or absent) `FurnaceType` with gas fuel and air medium may match, or list it explicitly as missing input.

## Guide Rule Gaps

### 3. Empty `FanBased/FanBasedDistributionType`

- Data: `Reference-PrimarySchool-L200-Audit.xml`, every delivery. `FanBased` holds an empty `<FanBasedDistributionType/>` next to `AirSideEconomizer` data. The element is optional in the schema.
- Guide: packaged rooftop, VAV, and PTAC/PTHP rows require `absent(A/FanBased/FanBasedDistributionType)` (or `Z/...`). An empty element fails that check, so economizer data blocks the match.
- Ask: treat an empty `FanBasedDistributionType` as absent, or require "no child elements" instead of "absent".

### 4. `CS/Quantity = 1` as a required predicate

- Data: `Reference-PrimarySchool-L200-Audit.xml`, VAV pods. The DX cooling sources omit `Quantity`.
- Guide: Packaged Rooftop VAV with Hot Water Reheat (and VAV with Hot Water Reheat, VRF) list `CS/Quantity = 1` under required cooling predicates, while other `Quantity` checks are guards that pass when absent.
- Ask: make `CS/Quantity` a guard (pass when absent), or confirm it must be supplied.

### 5. Integrated outdoor-air records

- Data: `Reference-PrimarySchool-L200-Audit.xml`. Per-zone `OtherHVACSystem` records with `VentilationType = Supply only` and `Integration = Integrated with central air distribution`, several linked to one VAV delivery, plus integrated records on PSZAC deliveries.
- Guide: only Stand-alone ventilation is defined. The guide does not say whether integrated records consume the linked delivery, so multiple records on one delivery read as a conflict, and an integrated record on a conditioned delivery reads as a conditioned DOAS.
- BOSS behavior: records with `Integration` `Integrated with central air distribution` or `Integrated with local air distribution` do not consume deliveries; they return `integrated`, and the linked deliveries are selected as conditioning deliveries.
- Ask: add this rule to the guide. `DemandControlVentilation` and `VentilationRate` on these records may later feed a modifier mapping.

### 6. `VentilationType None` or untyped ventilation on conditioned deliveries

- Data: ASHRAE L1/L2 exports (`Chula_Vista_ASHRAE_L*`, `Demo_ASHRAE_L2_Example_Building.xml`, `Example_ASHRAE_L2_Report_-_with_Energy_Use_Data*.xml`, `Example_HOMES_Template_Building.xml`, NYC files). `OtherHVACSystem` with only `MechanicalVentilation` (`VentilationType None` or none, optional `DemandControlVentilation`) links conditioned deliveries.
- Guide: the Explicitly no HVAC row covers only unconditioned deliveries; other cases are undefined.
- BOSS behavior: such records consume deliveries only when all linked deliveries are explicitly unconditioned. Otherwise the deliveries are selected as conditioning deliveries, and the record returns `no_hvac` (`None`) or `missing_input` (no type).
- Ask: add this rule to the guide.

### 7. Premises linked only on `HVACSystem`

- Data: every v2.7.0 fixture with detailed records links `LinkedPremises` on `HVACSystem`, not on `Delivery` or `OtherHVACSystem`.
- Guide: `zones(D)` and `zones(O)` come from the record's own links.
- BOSS behavior: a record without its own links inherits the parent `HVACSystem` links.
- Ask: add the fallback to the guide.

## Resolved Later

### 8. DX cooling source without a condenser plant

- Data: `example-smalloffice-level2.xml`, all five DX sources (`DXSystemType = Packaged/unitary heat pump`) omit `CondenserPlantIDs`.
- Guide: packaged and PTAC/PTHP/VRF rows require the DX condenser to resolve to an `AirCooled` condenser plant, so these deliveries identify no configuration.
- Ask: decide whether a packaged or terminal DX source without a condenser reference may be treated as air-cooled, or confirm it stays missing input.
- Resolution: packaged and terminal DX rows (PTAC, PTHP, packaged rooftop AC/HP/VAV) read an omitted `DX/CondenserPlantIDs` as air-cooled; a supplied reference must still resolve to a non-evaporative `AirCooled` condenser. VRF still requires the reference.
9 changes: 8 additions & 1 deletion docs/scenario_workflow_translation_plan.md
Original file line number Diff line number Diff line change
Expand Up @@ -278,12 +278,19 @@ Use this roadmap as the tracker. Keep `Status` and `Delivered by` current when a

### PR 14B: HVAC Selection Contract

- Status: Planned
- Status: In progress
- Delivered by: -
- Depends on: Can run in parallel with PR 14A.
- Scope: Read detailed HVAC data (sources, deliveries, plants, condensers, other HVAC systems, linked premises) and select topologies with the upstream guide's predicates. Shared by baseline and scenario workflows. Keep `get_principal_HVAC_system_type` for the existing baseline path.
- Done when: Table-driven tests cover exact matches and separate results for missing input, conflicting input, mapping gaps, and configurations with no gem measure.
- Avoid: Inferring topology from `MeasureName` or principal label alone, or dropping HVAC constituents silently.
- Implementation: `BOSS::HvacTopologySelector` (`lib/BOSS/hvac_topology_selector.rb`) returns one result per conditioning `Delivery` and per `OtherHVACSystem`, with status `match`, `mapping_gap`, `not_mappable`, `missing_input`, `conflicting_input`, or `no_hvac`, the `LinkedPremises` references, and a `group_key` (delivery, cooling source, plant tuple, or other-system ID). Family-only `PrincipalHVACSystemType` data returns `missing_input`.
- Deferred to later steps: guards comparing `Quantity` with zone counts and the premises-containment checks need the model crosswalk (PR 14C). Group-member consistency, zone-overlap checks, plant-binding limits, call ordering, and scenario `@Status` record selection belong to call construction (PR 14D/14E). `DuctSystems` checks are not implemented yet.
- Fixture follow-ups (found in PR 14D): a `Delivery` or `OtherHVACSystem` without its own `LinkedPremises` inherits the parent `HVACSystem` links (BuildingSync fixtures link premises only there; the upstream guide reads the record's own links). An `OtherHVACSystem` whose only content is `MechanicalVentilation` with `VentilationType` `None` or no type names no ventilation equipment; it owns its linked deliveries only when all of them are explicitly unconditioned. Otherwise those deliveries are selected as conditioning deliveries, and the record returns `no_hvac` (`None`, configuration "No separate ventilation equipment") or `missing_input` (no type). Fixture effect: ASHRAE-L2-style deliveries are now selected but return `conflicting_input`, because their `SourceHeatingPlantID` points to a plant in a different `HVACSystem` (cross-system plant references are not resolved yet). Whether the baseline planner may ignore `no_hvac` records is a PR 14D decision.
- Integrated outdoor air: an `OtherHVACSystem` with `Integration` `Integrated with central air distribution` or `Integrated with local air distribution` describes outdoor air through the linked deliveries' own air system. It does not consume those deliveries and returns the new status `integrated`; ERV, exhaust, and other not-mappable equipment still return `not_mappable`. Whether the planner may ignore `integrated` records is a PR 14D decision.
- Upstream guide rules adopted (buildingsync-measures-gem `e1b2f33`): Packaged Rooftop AC and Warm Air Furnace require a gas, air-medium `Furnace` and accept `FurnaceType` `Warm air`, `Other`, or absent. Packaged Rooftop Heat Pump accepts `HeatPumpBackupSystemFuel` `Electricity` or `Natural gas` and returns it in `Result#measure_arguments` as `supplemental_heating_fuel` (`Electricity`/`NaturalGas`). An empty `FanBasedDistributionType` counts as absent. `CS/Quantity` is a guard on the VAV and VRF rows. From `5e775a6`: packaged and terminal DX rows read an omitted `DX/CondenserPlantIDs` as air-cooled (VRF still requires it).
- L200 fixtures: `example-smalloffice-level2.xml` and `Reference-PrimarySchool-L200-Audit.xml` (copied from `../schema/docs/notebooks/bsync_examples/`) carry full Delivery/source/plant records. The L200 school now matches one Packaged Rooftop VAV with Hot Water Reheat and three Packaged Rooftop AC deliveries; VAV pods 2, 3, and other still return `conflicting_input` because they reference the `Boiler` plant defined in `VAV-Pod1` (resolving plants across `HVACSystem` records is open BOSS selector work). `example-smalloffice-level2.xml` now matches five Packaged Rooftop Heat Pump deliveries with `supplemental_heating_fuel` `NaturalGas`.
- Follow-up for PR 14C: `apply_hvac_topology_to_zone_scope` forwards only `operation`, `target_zone_names`, and `standards_template`. The binder and wrapper must forward `Result#measure_arguments` (for example `supplemental_heating_fuel`) before gas-backup heat pumps can run.