# ADR 0012: Heat control from a target temperature and a learned thermal twin

- Status: proposed.
- Implementation: the declaration
([#1995](https://github.com/srcfl/ftw/pull/1995)) and the twin in shadow
([#1996](https://github.com/srcfl/ftw/pull/1996)) are proposed as PRs.
Planned control has not shipped.
- Date: 2026-11-10
- Decided by: Fredrik on 10 November 2026, in his
[answers on #1994](https://github.com/srcfl/ftw/pull/1994#issuecomment-6763083595).
See [Decisions](#decisions).
- Builds on: [#520](https://github.com/srcfl/ftw/issues/520), the
[`thermal`](../../go/internal/thermal/model.go) contract, driver
[`controls`](../../go/internal/drivers/catalog_controls.go), the
[operator control API](../../go/internal/api/api_driver_control.go) and the
learned heating coefficient in [`loadmodel`](../../go/internal/loadmodel/model.go).
- Roadmap: Fredrik moves heat, space heat included, ahead of
[Heat: data first, bounded control later](../roadmap.md) and updates that
section and VISION.md himself.
- Layering: [#1772](https://github.com/srcfl/ftw/pull/1772). The twin and
the planner are a layer that proposes values; Core checks them.

## Context

Read against `master` at `7350a3e`:

- A driver can declare `controls` in its `DRIVER` block: an id, a label, an
evidence kind and one typed input with bounds. Heishamon declares
`set_heat_curve_offset` (−3..+3 °C, `write_ack`).
- `POST /api/drivers/{name}/control` sends a declared control, clamps it to
the declared bounds and holds it for at most 24 h. `DELETE` and expiry call
the driver's own `driver_default_mode`. The Heating view renders it.
- `thermal.DecideIntent` is a threshold rule over a temperature band and a
price. No package imports `thermal`.
- `loadmodel` learns a whole-house heating coefficient (W/°C) from load and
outdoor temperature. It has no indoor temperature, no inertia and no
control input.
- The control tick sends `battery`, `curtail` and the opt-in `solar_pv`
hint. Nothing sends a heat command.
- The Energyplan request already carries `thermal_loads` and the result
`thermal_power_w` and `thermal_state`, but protocol v1 marks thermal
inputs unsupported and Core rejects a non-empty thermal result
([contract](../energyplan-contract.md)).

A fixed threshold rule cannot answer the household's real question: *how
long can this house coast, and how early must it start?* That depends on the
building's inertia, the outdoor forecast and how strongly and how late the
device responds. These differ by orders of magnitude between a concrete
floor heated by a ground-source pump, a timber house with an air-to-air
unit, and a hot-water tank. An owner should not have to know or enter them.

## Decision

**The owner states a target temperature. A layer learns each zone's thermal
twin from what Core records: heat loss, inertia, and how the device's control
moves the temperature. A planner in the same layer uses the twin, prices,
solar and weather forecasts to propose the control value for each slot
(on/off, setpoint or offset) that keeps the predicted temperature on target
at the lowest cost, so heat joins battery and car in one plan of
flexibility. Core checks every proposed value against what Core owns: the
declared bounds, the lease, the minimum on and off times, and release to the
device when a reading is stale or missing.** Core never learns a device by
name, and Core is not what limits which devices work: support is claimed per
driver, with hardware evidence.

### 1. What the owner sets

A zone is one comfort sensor with its own target. A house has as many zones
as it has sensors the owner cares about. Each is off by default. The driver
names below are examples of what a site might run; Core names none:

```yaml
thermal:
zones:
- id: living
enabled: true
comfort_sensor: { driver: wiser, metric: room_living_temp_c }
target_c: 21.0
flex_c: 1.0 # how far the planner may move away from target
controls:
- { driver: heishamon, id: set_heat_curve_offset } # shared source
- { driver: wiser, id: set_room_living_setpoint } # this room only
- id: bedroom
enabled: true
comfort_sensor: { driver: wiser, metric: room_bedroom_temp_c }
target_c: 18.0
flex_c: 1.5
controls:
- { driver: heishamon, id: set_heat_curve_offset }
- { driver: wiser, id: set_room_bedroom_setpoint }
- id: hot_water
enabled: true
comfort_sensor: { driver: heishamon, metric: hp_dhw_temp_c }
target_c: 60.0
flex_c: 5.0 # the band 55-65 °C; see the hot-water floor below
controls:
- { driver: heishamon, id: set_dhw_mode }
```

- `target_c` is the goal for that zone alone. An optional schedule may
change it over the day later; this ADR does not add one.
- A zone lists every control that heats it. A control listed by several
zones is a **shared source**, such as one heat pump's curve offset serving
every room. A control listed by one zone is **local**, such as a room
thermostat or a valve.
- `flex_c` is the owner's trade between comfort and savings. Around the
target it gives the hard band `[target − flex, target + flex]`, which the
learned twin may never widen.
- **A hot-water zone has a floor, with a short dip allowed.** For a zone
whose comfort sensor is declared `asset = "dhw"`, measured at the top of
the tank where water is drawn:
- The band never goes below a **floor of 50 °C**, whatever `target_c` and
`flex_c` say. Core rejects a configuration that does.
- After a draw, such as a shower, the planner may hold off reheating so it
can wait for cheaper energy. The tank may then sit under the floor for at
most **2 hours** at a time, and never under **45 °C**.
- When either limit is reached, Core releases the tank to the device,
which reheats by its own regulation. Core keeps the timer, so this does
not depend on the layer.

The reason is Legionella. It multiplies between about 20 and 45 °C, and
the risk is water that stays lukewarm for days, not a dip of a few hours:
industry sources give a doubling time of 2–6 hours at best, around
37–42 °C in stagnant water with biofilm, and days to weeks to reach high
counts in real systems. The Swedish building rules ask for at least 50 °C
at the tap
([BFS 2024:8](https://www.boverket.se/sv/PBL-kunskapsbanken/regler-om-byggande/hygien-halsa-och-miljo/vatten-avlopp/legionella/),
chapter 8, section 6), and Boverket recommends 60 °C in the water heater.
German guidance for single-family houses says to avoid running below
50 °C. The three numbers are proposed, not decided; see [Open](#open).
- Without a comfort sensor, a zone cannot be planned. The roadmap does not
let Core assume indoor temperature.

### 2. Declaration by the driver

Two optional fields on an existing control, an optional `sensors` list and
optional device protection timings. A control without `asset` and
`strategy` stays operator-only.

```lua
controls = {
{
id = "set_heat_curve_offset", label = "Heat curve offset",
evidence = "write_ack",
asset = "space_heat", -- space_heat | dhw | cooling | buffer
strategy = "curve_offset", -- curve_offset | setpoint | on_off | discrete_mode
zone = "z1",
min_interval_s = 600, -- vendor rate limit or wear
device_hold_max_s = 3600, -- the device reverts by itself after this
input = { type = "number", min = -3, max = 3, step = 1, unit = "°C", default = 0 },
},
{
id = "set_power", label = "Heating on",
asset = "space_heat", strategy = "on_off",
min_on_s = 1200, min_off_s = 900, -- compressor protection
input = { type = "boolean" },
},
},
sensors = {
{ metric = "hp_indoor_temp_c", asset = "space_heat", zone = "z1" },
{ metric = "hp_dhw_temp_c", asset = "dhw" },
},
```

- `on_off` covers devices whose only lever is start/stop. The driver's
`min_on_s` and `min_off_s` are hard constraints on the plan, not
preferences.
- **The lease.** `device_hold_max_s` says the device itself keeps a value
for at most that long and then returns to its own regulation, such as a
hub's timed boost or override. Core sends each planned value with a hold
no longer than that and renews it while the plan stands. If FTW stops,
crashes or loses power, the device falls back on its own. A control
without a device-side hold may still be planned, but only within one
declared `step` of its declared `input.default`. Without both a default
and a step, it gets no planned control.
Two holds seen on hardware: a Wiser hub's room override sent with
`DurationMinutes` ends on a quarter hour and returns the room to its
manual setpoint or schedule by itself, and CTC's 1000-series registers
reset five minutes after the last write.
- Supporting a device is a driver's work: a user can write a driver for
their own device, declare these fields and test it. Support is claimed
per driver with hardware evidence, not by Core.
- `sensors` names metrics a driver already emits. Any driver can supply
them, so a room thermostat's sensor can judge a heat pump driven by
another driver.
- The parser ignores unknown fields, so existing drivers are unaffected.

### 3. The thermal twin

One first-order model per zone, learned in a layer beside `loadmodel` and
the per-battery response model. It reads what Core records and never holds
up the control loop:

```text
C · dT_in/dt = G(u, T_out) − UA · (T_in − T_out)
```

| Learned term | Meaning | Learned from |
|---|---|---|
| `UA` | heat loss, W/°C | indoor, outdoor and heat input; seeded from `loadmodel` |
| `τ = C/UA` | inertia: how long the zone coasts | indoor temperature drift while input is steady |
| `G(u, T_out)` | how much heat the control value delivers | indoor response to past control changes |
| dead time | how late the response starts | the same, as a delay |

For a hot-water tank or buffer, the same form describes the store's
temperature, standing loss and fill rate.

- **Shadow first.** A new twin only predicts. It is compared with the
measured temperature and is not used for control.
- **Confidence gate.** A zone gets planned control only while its twin is
trusted: its prediction error has stayed under a limit across a stated
period. An untrusted twin gives no planned control, and the device runs
itself. The twin's state ("learning", "trusted", "drifting") and its error
are shown to the owner.
- **Learning from ordinary operation.** The twin learns from what the device
does by itself and from owner holds. The planner makes no steps only to
learn.
- **A zone's neighbours.** A zone inside a heated house loses much of its
heat to the zones around it, not straight outdoors. A tiled bathroom
with electric floor heating sits between rooms the heat pump keeps warm.
Fitted against `T_out` alone, its `UA` is an effective value that holds
only while the neighbours stay as they are; warming the house lowers
the zone's need. Where a neighbouring zone's temperature is declared,
the twin uses it as a second boundary.
- The twin is advisory, as [safety.md](../safety.md#planner-and-model-containment)
requires. It never widens the band or a declared limit, and its prediction
never counts as evidence. Only the measured temperature verifies a plan.

### 4. The planner

- **A planning layer proposes; Core checks.** A dynamic program over the
existing price, PV and weather horizon. Its state is the predicted zone
temperature, and the actions are the declared control values, few by
construction (for example seven offsets, or on/off). The cost is energy
at its marginal price plus a penalty for distance from the target. The
band and the `min_on_s`/`min_off_s` timings are constraints of the plan.
Core checks them again on every value it is asked to send.
- **Zones are planned together.** Every enabled zone must stay inside its
own band. A shared source is planned once for all the zones it serves, so
the zone that needs the most heat sets it. Local controls then trim each
room toward its own target, and the twin of each zone learns its response
to both. A shared source is never raised beyond what keeps the warmest
zone inside its band, unless that zone's local control can hold it back.
When no value satisfies every zone, the plan is infeasible. The shared
source is then released to the device and the conflict is shown to the
owner, not hidden by favouring one room. There is no zone ranking.
A released source stays with the device for at least 1 hour, and is
taken back only when a plan keeps every zone inside its band for that
whole hour. The owner is told once per conflict, not once per slot. A
conflict that comes and goes therefore costs at most one release and one
reclaim an hour, never one per slot.
- **Cost per kWh of heat, not of electricity.** Each heat input is
costed as electricity at the slot's price divided by its efficiency: 1
for direct electric heat, the learned COP at that outdoor and supply
temperature for a heat pump. Storing heat in a cheap slot pays only when
the price ratio beats the efficiency ratio plus the extra loss. A tiled
floor charged with direct electric heat (COP 1) in a house that a heat
pump also heats (COP 3-4 at 4 °C outdoor) rarely pays, even at a price
spread of 1.5; the same hours spent raising the heat pump's flow can.
When two sources can warm one zone, the planner prefers the cheaper heat
per kWh, not the cheaper electricity.
- **The planner works out the buffering itself.** It preheats before an
expensive period exactly as far as the learned inertia lets the zone
coast, and stores PV surplus as heat where the twin says it will last.
- **Energyplan can take over later** through the reserved `thermal_loads`
and `thermal_state` fields, behind an explicit worker capability, as
`hourly_import_caps` did. Core then validates its trajectory against the
same bounds and keeps the Go planner as fallback.
- `thermal.DecideIntent` and the other unused `thermal` code are removed.
Without a trusted twin there is no rule-based fallback: the device runs
itself.

### 5. Dispatch and ownership

- A heat block in the control tick, after the solar feed, on
freshness-allowed ticks only. A stale site meter already defaults every
driver.
- Write when the planned value changes, and renew the device-side hold
before it ends. Never faster than `min_interval_s`.
- One owner per driver. Operator holds and planned commands share the
per-driver state now in `api`, moved to a package both can use. An
operator hold wins. The planner treats the held control as fixed at its
held value for every zone it serves, and plans the rest around it until
the hold ends.
- Each slot records the planned value, the command, the driver result, the
predicted temperature and the measured temperature. That is the evidence
the product rules ask for, and it is what the twin learns from.

### 6. Safety

Each protection follows [safety.md](../safety.md#clamp-discipline). Core
owns the first group. The layer's checks only decide what it proposes, and
Core does not rely on them.

| Owner | Condition | Limit | Reaction and recovery |
|---|---|---|---|
| Core | Value outside the declared input | declared min/max | clamp (exists today) |
| Core | No device-side hold | one `step` from `input.default` | refuse a value beyond it |
| Core | FTW stops renewing | `device_hold_max_s` | the device reverts by itself |
| Core | Comfort reading stale or missing | the watchdog timeout | release to device; resume on a fresh reading |
| Core | Short cycling | `min_on_s`, `min_off_s` | refuse a value that breaks it |
| Core | Writes too frequent | `min_interval_s` | skip; the next due slot sends |
| Core | Hot-water zone band under the floor | 50 °C | reject the band in config |
| Core | Hot-water zone under the floor too long or too far | 2 h under 50 °C, or under 45 °C | release the tank to the device; resume above the floor |
| Layer | Measured temperature outside the band | owner band | propose release; resume back inside |
| Layer | Twin not trusted, or error over limit | confidence gate | propose nothing; the device runs itself |
| Layer | Zones conflict on a shared source | every zone's band | release the source and tell the owner |

The site-meter and watchdog paths stay ahead of all of these.

When the layer is down, nothing reacts to a measured temperature outside the
band. That case rests on the lease alone: a device with a device-side hold
returns to its own regulation within `device_hold_max_s`, and a control
without one can never be more than one `step` from its `input.default`. The
hot-water floor does not depend on the layer, because Core owns it.

### Not in scope

Temperature schedules, the Live Energy node for heat pumps (#520, part 1),
the Settings form and an Energyplan thermal capability. Each is a separate
change.

## Decisions

Fredrik answered on 10 November 2026:

1. **Order.** Go ahead, starting with the twin in shadow. Heat pumps, space
heat included, belong in FTW as long as the base model is good. Planning
flexibility across battery, car and heat is the goal.
2. **Lease.** Planned control needs the device to fall back on its own,
through a device-side timed hold. Otherwise planned values stay a small
step from the device default.
3. **Untrusted twin.** No planned control; the device runs itself.
`thermal.DecideIntent` and the other unused `thermal` code are removed.
4. **Learning steps.** Not for now. The twin learns from ordinary operation
and owner holds.
5. **Zone conflicts.** Release the shared source and tell the owner. No zone
ranking.
6. **First case.** None named in Core. Build the generic base so that a user
can write and test a driver for their own device. Support is claimed per
driver, with hardware evidence.
7. **Keep the core simple.** Core owns the declared bounds, the lease, the
minimum on and off times, and release to the device when a reading is
stale or missing. The twin and the planner are a layer that proposes
values, and Core checks them.

## Open

- **The hot-water floor.** Proposed: a 50 °C floor, a dip under it of at
most 2 hours, and never under 45 °C, for Fredrik to confirm or change. The
growth figures behind them are industry sources, not measurements, so the
numbers lean cautious. A periodic pass to 60 °C or more against
Legionella is a later, separate change.
- **Holding off a reheat needs a control.** Many heat pumps start a
hot-water charge by themselves at their own start temperature. The planner
can only delay a reheat on a device whose driver declares a control that
blocks or lowers the charge.
- **Where the efficiency comes from.** Proposed: a control declares its
heat source (`direct_electric` or `heat_pump`); a heat pump's COP is
learned from its metered electrical input where a driver reports one,
and otherwise taken from a declared curve. Some controllers, such as the
CTC EcoZenith, report no compressor power, so the curve is all there is.
- **How long a released shared source stays released.** Proposed: at least
1 hour, reclaimed only when a plan keeps every zone in its band for that
hour. The hour is a starting value to tune on hardware.